3.2Draft

Manometers and test points

Connecting, zeroing and reading U-gauge and digital manometers.

About 10 minIGEM/UP/1B Edition 4BS 6891:2015

This topic supports

  1. M03.2Connect and read a manometer to measure standing, working and operating pressures.

Draft: this lesson hasn't yet been technically reviewed.

A is how you see what the gas is doing. A reading is only useful if the gauge is right for the job, set up properly and connected to the right point.

Interactive artefact

Manometers on a test point

U-gauge and digital manometer on a test point: standing versus working pressure as appliances fire.

Will demonstrate

  • Connecting a U-gauge and a digital manometer to a test point
  • Reading standing pressure with appliances off
  • Watching working pressure as appliances fire

Planned. This interactive will appear here when it's built.

Choosing and looking after a gauge

Any gauge must be suitably ranged, suitable for the gas and for the place it's used in, and calibrated as its manufacturer requires.

Water (U-gauge)Electronic
Must read to0.5 mbar0.1 mbar
CalibrationNot needed, but keep it well maintainedAt least every 12 months (or as the manufacturer says), with a certificate
Before useZero itZero it, use it within its temperature range, and let it settle to room temperature first, because electronic gauges can drift as the temperature changes

A display that shows lots of decimal places isn't necessarily that accurate. Check the gauge and its tubing for leaks immediately before taking a reading. If you're in a place where there may be gas in the air, the gauge may need to be certified for hazardous areas (see 6.5).

Where the test points are

  • The meter: use the meter installation's test point where it has one. Where there's no meter test point, BS 6891 requires one no more than 300 mm after the ECV or AECV.
  • Each appliance: a test point at the appliance inlet, if the appliance doesn't have a suitable one of its own. It can be built into the isolation valve.
  • Inside the appliance: test points on the gas valve for inlet and burner pressure, as the manufacturer's instructions show.

Taking a reading

  1. Zero the gauge, and connect it with suitable tubing.
  2. Open the (undo or remove its test screw), and connect the tube.
  3. Take the reading under the conditions the check calls for (all appliances off for standing pressure, for example, or at high load; see 3.3).
  4. Remove the gauge, close the test point, turn the gas back on if needed, and test the test point with leak detection fluid.

Sources: IGEM/UP/1B Ed. 4 4.1gauges BS 6891:2015 8.6test points CCN1 Issue 16 §10 PC 1–4, K&U 4measuring OP

Tutor notes
  • Have learners connect both a U-gauge and an electronic gauge to the same test point and compare readings.
  • Ask why an electronic gauge carried in from a cold van might read wrongly for the first few minutes.
  • CCN1 §10 knowledge item 4 covers using an electronic gauge and its calibration.